Accepta 2314
Corrosion Inhibitor & Scale Dispersant
Recirculating Water System Cleaner (for on line and off line clean up)
Open Evaporative Cooling Systems
Closed Cooling Systems
Accepta
2314 is a high performance chlorine
stable, nonvolatile cooling water corrosion inhibitor and scale dispersant scientifically formulated
for the treatment and protection of open evaporative cooling systems and closed cooling systems.
Accepta 2314 is the best choice to solubilize and
disperse mill scale, rust, mineral scale, mud, oil, grease and organics that
foul in new and old piping systems.
A superior alkaline formulation, Accepta 2314 is a highly efficient corrosion inhibitor, threshold deposit controller and sludge conditioner, whilst offering protection to multimetal systems
without the requirement of additional
specific corrosion inhibitors.
Accepta 2314 is environmentally sensitive being free from any of the
controversial constituents such as heavy metals or phosphates, whose use is
becoming increasingly restricted.
Offering the same superior
protection over an extended range of pH, temperature and raw water hardness, Accepta 2314 is the ideal treatment for
both building services and facilities installations and industrial
applications.
Product Benefits
High performance
corrosion inhibitor and scale dispersant Chlorine stable, nonvolatile product
Suitable for both open
evaporative cooling systems and closed cooling systems
Alkaline blend
Effective corrosion inhibitor, threshold deposit controller
and sludge conditioner Multimetal
use without additional chemicals
Free from heavy
metals and phosphates
Can be used over
wide range of pH, temperature and water hardness Suitable for building services
and industrial applications
Product Properties
Form: Liquid
Colour: Yellow
Odour: Slight ammonia
pH: 12 13
Relative
density: 1.2 1.3 Solubility in
water: Miscible Flammability: Noncombustible
*Full details of the product properties are available in
the Safety Data Sheet. See below.
Application & Dosage Information
PreTreatment
Dosage
To ensure rapid film
formation and corrosion control the system should be pretreated with Accepta
2314 for two or three weeks at twice
the normal continuous dosage.
Continuous Dosage
Accepta 2314 should be dosed to maintain a reserve of 50ml/m3 in recirculation. For maximum control
and economy it should be dosed continuously, excellent results being
achieved employing an automatic proportional
dosing unit.
It is always advisable to carry out a 'Control Of Substances Hazardous
to Health' (COSHH) assessment before use.
For further technical assistance concerning Accepta 2314
please contact Accepta.
For on line clean
up recommended dosage 1,800 - 1,950ppm in the system for a period of 24 - 48
hours.
Safety, Storage & Handling
For full details concerning safety precautions, storage and handling
procedures for Accepta 2314 please
refer to the latest Safety Data Sheet. To
download the latest safety data for this product use the following link: